Mighty,Module,MM7501,DC Input,Integrating,Totalizer,Pulse,Output,Transmitter

Mighty Module MM7501 DC input Integrating Totalizer Pulse Output Transmitter


MM7501 DC input Integrating Totalizer Pulse Output Transmitter

Mighty,Module,MM7501,DC Input,Integrating,Totalizer,Pulse,Output,TransmitterDescription

The MM7501 is used, together with a counter, to integrate or totalize flow and other signals. Its output is a pulse rate proportional to a DC input. When totalized on a counter, the pulses indicate the total flow or other quantity being measured.

Typical input ranges are 4/20 mA, 10/50 mA, 0-1 V, 0-5 V, and 0-10 VDC. Other ranges are available down to minimum spans of 1 V or 1 mA DC.

The MM7501 includes a frequency scaler (binary pulse rate divider) which, together with wide-ranging zero and span controls, provides a 4096:1 range of output pulse rate adjustment.

This allows the output to be scaled in engineering units (one pulse equals 1,000 gallons, for example). The output may be an spdt relay, a voltage pulse suitable for driving a 12 V electromechanical, counter or an open collector output.

The module includes filtering and conditioning to reduce susceptibility to transients and noisy operations. An integrating DC to frequency converter generates the basic pulse rate.

Mighty,Module,MM7501,DC Input,Integrating,Totalizer,Pulse,Output,Transmitter Download MM7501 Brochure

Mighty,Module,MM7501,DC Input,Integrating,Totalizer,Pulse,Output,Transmitter Download MM7501 Manual

Features

Mighty,Module,MM7501,DC Input,Integrating,Totalizer,Pulse,Output,Transmitter
Provides an Output Pulse Rate Proportional to the DC Input
Mighty,Module,MM7501,DC Input,Integrating,Totalizer,Pulse,Output,Transmitter
1 V or 1 mA Minimum Input Span
Mighty,Module,MM7501,DC Input,Integrating,Totalizer,Pulse,Output,Transmitter
Unlimited* Choice of Input/Output Ranges
Mighty,Module,MM7501,DC Input,Integrating,Totalizer,Pulse,Output,Transmitter
Choice of Power Options
Mighty,Module,MM7501,DC Input,Integrating,Totalizer,Pulse,Output,Transmitter
10 + 5 Year Warranty

Typical Applications

Totalizing flow, BTU, or any other quantity that can be represented in quantity per unit time.

Mounting

The MM7501 is designed to plug into a standard 8-pin relay socket. Part number MP008 is a molded plastic socket suitable for mounting on a flat surface or in a 2 3/4 inch wide PVC snap track (TRK48).  Use CLP-1 hold-down clip, if needed. A Killark HK Series explosion-proof housing with dome and 8-pin socket is available (HKB-HK2D-8).  A DIN rail mounted socket (DMP008) is available for 35mm symmetrical DIN rail.

Specifications

INPUT RANGE
Voltage
  select any range between ±10 V
    (min span 1 V)

Current
  select any range from 0 to 100 mA max
    (min span 1 mA)

INPUT IMPEDANCE
Voltage
  1 megohm

Current
  2.0 V drop typical,
    others available

OUTPUT RANGE
7 pph min to 8 pps max at 20 mA input
  1 pps max with relay
    (user adjustable)

TYPE OUTPUT
Relay 
  (standard)
   spdt, 1 A contact

Transistor
  (Option OC)
  open-collector npn
  transistor, sink
  0.5 A, 24 V max

Pulse
  (Option V)
  12 V
  60 msec pulse width
  (others available)

ACCURACY
+/-0.1% of span

LINEARITY
+/-0.1% of span

BREAKDOWN, P0WER/CIRCUITRY
>1500 VAC rms

OPERATING TEMPERATURE
 14°F to 140°F
-10°C to  60°C

TEMPERATURE STABILITY
±0.4% of span/°C max

POWER
115 VAC ±10%, 50/60 Hz
  (2.5 W max)

230 VAC ±10%, 50/60 Hz
  (2.5 W max)

DC Power Option
  24 VDC
    (limits 21-32 VDC)
    (2.5 W max)
  Isolation
    DC power supply to input common:
      10 megohms

 

* Within specified range limits

 


CONNECTIONS
Power AC L1 or DC +
Power AC L2 or DC -
Input +
Input -

Relay Output
Output NC
Output C
Output NO

Option 'OC' or 'V'
Output +
Output -

PINS
1
3
4
 5

 
6
7
8

 
7
8