The MM4410 provides a DC output voltage or current proportional to the product of two DC inputs. Typical input ranges are 4/20 mA, 0/50 mA, 0-1 V, 0-5 V, and 0-10 VDC. Other ranges are available down to minimum spans of 1 V or 1 mA DC. Standard calibration provides the output at full scale (100%) when both inputs are at full scale (100%). Other calibrations are available.

The module includes filtering and conditioning to reduce susceptibility to transients and noisy operations.

Mighty,Module,MM4410,DC Input,Multiplier,Transmitter Download MM4410 Brochure

Mighty,Module,MM4410,DC Input,Multiplier,Transmitter Download MM4410 Manual

Features

Mighty,Module,MM4410,DC Input,Multiplier,Transmitter
Provides DC Output Proportional to the Product of Two DC Inputs (Output = A x B)
Mighty,Module,MM4410,DC Input,Multiplier,Transmitter
Fully Isolated Output Available
Mighty,Module,MM4410,DC Input,Multiplier,Transmitter
1 V or 1 mA Minimum Input Span
Mighty,Module,MM4410,DC Input,Multiplier,Transmitter
Unlimited* Choice of Input/Output Ranges
Mighty,Module,MM4410,DC Input,Multiplier,Transmitter
Choice of Power Options
Mighty,Module,MM4410,DC Input,Multiplier,Transmitter
10 + 5 Year Warranty 

Typical Applications

Calculating power (current x voltage), mass flow (flow rate x density), etc.

Mounting

The MM4410 is designed to plug into a standard 8-pin relay socket. Part number MP008 is a molded plastic socket suitable for mounting on a flat surface or in a 2 3/4 inch wide PVC snap track (TRK48). Use CLP-1 hold-down clip, if needed. A Killark HK Series explosion-proof housing with dome and 8-pin socket is available (HKB-HK2D-8). A DIN rail mounted socket (DMP008) is available for 35mm symmetrical DIN rail.

Specifications

INPUT RANGE
Voltage
  select any range between ±250 V
    (min span 1 V)

Current
  select any range between ±100 mA max
    (min span 1 mA)

INPUT IMPEDANCE
Voltage
  100 kilohms

Current
  1.25 V drop typical,
    others available

OUTPUT RANGE
Voltage
  select any range from  -10 V to +15V
  10 mA max load
    (min span 0.2 V)

Current
  select any range from 0 to 50 mA max
    (min span 1 mA)
  24 V compliance**
    18 V compliance for ISO option
    if full scale output >20 mA

RESPONSE TIME
< = 150 ms

ACCURACY
 ±0.25% of span

 

ISOLATION (Optional)
Output/Input
  >500 megohms

Breakdown Voltage
  >1000 VAC rms

OUTPUT RIPPLE
<0.1% of span
  (peak to peak)

BREAKDOWN, P0WER/CIRCUITRY
>1500 VAC rms

OPERATING TEMPERATURE
 14°F to 140°F
-10°C to  60°C

TEMPERATURE STABILITY
±0.02% of span/°C max

POWER
115 VAC ±10%, 50/60 Hz
  (2.5 W max)

230 VAC ±10%, 50/60 Hz
  (2.5 W max)

DC Power Option
  24 VDC
    (limits 21-32 VDC)
    (2.5 W max)
  Isolation
    DC power supply to input common:
      10 megohms

* Within specified range limits

** Compliance:  The sum of all voltage drops in the output loop cannot exceed 24V at rated current (1200 ohms 20 mA).

CONNECTIONS
Power AC L1 or DC +
Power AC L2 or DC -
Input B +
Input A +
Input -
Output +
Output -
PINS
1
3
4
5
6
7
8