Mighty,Module,MM4130,Thermocouple,Input,Isolated,Transmitter

Mighty Module MM4130 Thermocouple Input Isolated Transmitter


MM4130 Thermocouple Input Isolated Transmitter

Description

The MM4130 provides a DC output voltage or current, fully isolated from input, line power and ground, proportional to a thermocouple input signal. It is useful in measuring temperatures with any type of thermocouple.  Cold junction compensation is provided by a solid state temperature sensor embedded in the thermocouple terminal strip. The module also includes filtering and conditioning to reduce susceptibility to transients and noisy operations.

The module utilizes a feedback VCO to develop a pulse train with a duty cycle proportional to the input signal amplitude. This pulse train is coupled through a pulse transformer to the output circuitry where the duty cycle data is converted to a proportional DC level in the output circuit. The isolated output eliminates ground loops, large common mode signals and other types of interference.

Upscale burnout protection is provided as standard. In the event the thermocouple opens, the transmitter output will go off scale high. Option B provides downscale burnout protection (transmitter output goes low).

Mighty,Module,MM4130,Thermocouple,Input,Isolated,Transmitter Download MM4130 Brochure

Mighty,Module,MM4130,Thermocouple,Input,Isolated,Transmitter Download MM4130 Manual

Features

Mighty,Module,MM4130,Thermocouple,Input,Isolated,Transmitter
Provides a Fully Isolated DC Output Proportional to any Thermocouple Input
Mighty,Module,MM4130,Thermocouple,Input,Isolated,Transmitter
Cold Junction Compensated
Mighty,Module,MM4130,Thermocouple,Input,Isolated,Transmitter
4 mV Minimum Input Span
Mighty,Module,MM4130,Thermocouple,Input,Isolated,Transmitter
Unlimited* Choice of Input/Output Ranges
Mighty,Module,MM4130,Thermocouple,Input,Isolated,Transmitter
Upscale Burnout Protection (Downscale Available)
Mighty,Module,MM4130,Thermocouple,Input,Isolated,Transmitter
Choice of Power Options
Mighty,Module,MM4130,Thermocouple,Input,Isolated,Transmitter
10 + 5 Year Warranty

Typical Applications

Eliminates ground loops and common mode signals for temperature monitoring, control, and data acquisition.

Mounting

The module is designed to plug into a standard 8-pin relay socket. Part number MP008 is a molded plastic socket suitable for mounting on a flat surface or in a 2 3/4 inch wide PVC snap track (TRK48).  Use CLP-1 hold-down clip, if needed. A Killark HK Series explosion-proof housing with dome and 8-pin socket is available (HKB-HK2D-8).  A DIN rail mounted socket (DMP008) is available for 35mm symmetrical DIN rail.

Specifications

INPUT RANGE
select any type TC
  (min span 4 mV)

OUTPUT RANGE
Voltage
  select any range from  -10 V to +15V
  10 mA max load
    (min span 0.2 V)

Current
  select any range from 0 to 50 mA max
    (min span 1 mA)
  24 V compliance**
    18 V compliance if full scale output >20 mA

OUTPUT RIPPLE
<0.1% of span
  (peak to peak)

ACCURACY
±0.1% of span at endpoints

LINEARITY
Output/Input
+/-0.05% of span
  (non-linearized)

COMMON MODE REJECTION
120 dB, DC to 60 Hz

ISOLATION
Output/Input
  >500 megohms

Breakdown Voltage
  >1000 VAC rms

BREAKDOWN, P0WER/CIRCUITRY
>1500 VAC rms

OPERATING TEMPERATURE
 14°F to 140°F
-10°C to  60°C

TEMPERATURE STABILITY
±(0.02% of span + 1.3 µV)/°C max

POWER
115 VAC ±10%, 50/60 Hz
  (2.5 W max)

230 VAC ±10%, 50/60 Hz
  (2.5 W max)

DC Power Option
  24 VDC
    (limits 21-32 VDC)
    (2.5 W max)
  Isolation
    DC power supply to input common:
      10 megohms


* Within specified range limits

** Compliance:  The sum of all voltage drops in the output loop cannot exceed 24V at rated current (1200 ohms 20 mA).

CONNECTIONS
Power AC L1 or DC +
Power AC L2 or DC -
Input +
Input -
Output +
Output -
PINS
1
3
T/C Terminal +
T/C Terminal -
7