Mighty Module MM1820 Potentiometer Position Input Dual Limit Alarm
MM1820 Potentiometer Position Input Dual Limit Alarm Description The MM1820 monitors the slide position of a potentiometer and provides two sets of spdt, 5 A alarm relays with two independently adjustable setpoints. Each setpoint has a set of red/green LEDs to indicate alarm status. When the signal exceeds a particular setpoint, the relay becomes energized. To provide a fail safe operation (loss of power resulting in alarm state),select Option RR. The module can be supplied as a HI/HI, HI/LO, or LO/LO alarm (HI/LO supplied if not specified). Standard deadband on both alarms is fixed at 0.5% of span. (Option A provides adjustable deadband of 0.5% to 100% of span.) Option D, latching alarms has no deadband control. Once the limit has been reached, the alarm latches and power to the module must be momentarily interrupted to reset the alarm. The module includes filtering and conditioning to reduce susceptibility to transients and noisy operations. It also utilizes a stable 1 V power supply to excite the potentiometer. Any value potentiometer from 100 ohms to 100 kilohms can be used. Features
Typical Applications Tank level, valve or actuator position control, monitoring or warning. Mounting The module is designed to plug into a standard 11-pin relay socket. Part number MP011 is a molded plastic socket suitable for mounting on a flat surface or 2 3/4 inch wide PVC snap track (TRK48). Use CLP-1 hold down clip if needed. A Killark HK Series explosion-proof housing with dome and 11-pin socket is available (HKB-HK2D-11). A DIN rail mounted socket (P/N DMP011) is available for 35mm symmetrical rail. Specifications
|