Mighty Module MM1520 Strain Gauge (Bridge) Input Dual Alarm
MM1520 Strain Gauge (Bridge) Input Dual Alarm
Description The MM1520 monitors the DC input signal from a strain gauge bridge and provides two sets of spdt, 5 A alarm relays with two independently adjustable setpoints. Each setpoint has a set of red/green LEDs to indicate alarm status. When the input is between the setpoints, the relays are normally de-energized. When the signal exceeds a particular setpoint, the relay becomes energized. To provide a fail-safe operation (loss of power resulting in an alarm state), select Option RR. The Module can be supplied as a HI/HI, HI/LO, or LO/LO alarm (HI/LO supplied if not specified). Standard deadband on both alarms is fixed at 0.5% of span. (Option A provides adjustable deadband of 0.5% to 100% of span.) Option D, latching alarms, has no deadband control. Once the limit has been reached, the alarm latches and power to the Module must be momentarily interrupted to reset the alarm. The Module includes filtering and conditioning to reduce susceptibility to transients and noisy operations. It also provides a well regulated excitation voltage for the strain gauge and a high quality differential preamplifier to condition the low level output from the bridge. Features
Typical Applications Weight and pressure control, monitoring or warning. Mounting The Module is designed to plug into a standard 11-pin relay socket. Part number MP011 is a molded plastic socket suitable for mounting on a flat surface on 2 3/4 inch wide PVC snap track (TRK48). Use CLP-1 hold-down clip if needed. A Killark HK Series explosion-proof housing with dome and 11-pin socket is available (HKB-HK2D-11). A DIN rail mounted socket (P/N DMP011) is available for 35mm symmetrical rail. Specifications
|