Mighty,Module,MM1020,DC Input,Dual Limit Alarm,Two,SPDT,Relays,Fixed,Range

Mighty Module MM1020 DC Input Dual Limit Alarm Two SPDT Relays Fixed Range


MM1020 DC Input Dual Limit Alarm Two SPDT Relays Fixed Range

Mighty,Module,MM1020,DC Input,Dual Limit Alarm,Two,SPDT,Relays,Fixed,RangeDescription

The MM1020 monitors a DC input signal and provides two sets of spdt, 5 A alarm relays with two independently adjustable setpoints. Each setpoint has a set of red/green LEDs to indicate alarm status. When the input is between the setpoints, the relays are normally de-energized. When the signal exceeds a particular setpoint, the relay becomes energized. To provide a fail-safe operation (loss of power resulting in an alarm state), select Option R. The module can be supplied as a HI/HI, HI/LO, or LO/LO alarm (HI/LO supplied if not specified).

Standard deadband on both alarms is fixed at 0.5% of span.  (Option A provides adjustable deadband of 0.5% to 100% span.) Option D, latching alarms, has no deadband control. Once the limit has been reached the alarm latches and power to the module must be momentarily interrupted to reset the alarm.

The module includes filtering and conditioning to reduce susceptibility to transients and noisy operations.

Mighty,Module,MM1020,DC Input,Dual Limit Alarm,Two,SPDT,Relays,Fixed,Range Download MM1020 Brochure

Mighty,Module,MM1020,DC Input,Dual Limit Alarm,Two,SPDT,Relays,Fixed,Range Download MM1020 Manual

Features

Mighty,Module,MM1020,DC Input,Dual Limit Alarm,Two,SPDT,Relays,Fixed,Range Provides Relay Contact Closures at Preset DC Input
Mighty,Module,MM1020,DC Input,Dual Limit Alarm,Two,SPDT,Relays,Fixed,Range Fail-safe, Latching and Adjustable Deadband Available
Mighty,Module,MM1020,DC Input,Dual Limit Alarm,Two,SPDT,Relays,Fixed,Range Red and Green LED Alarm Status Indicators
Mighty,Module,MM1020,DC Input,Dual Limit Alarm,Two,SPDT,Relays,Fixed,Range 50 mV or 1 mA Minimum Input Span
Mighty,Module,MM1020,DC Input,Dual Limit Alarm,Two,SPDT,Relays,Fixed,Range Unlimited* Choice of Input Ranges
Mighty,Module,MM1020,DC Input,Dual Limit Alarm,Two,SPDT,Relays,Fixed,Range Wide Range Input Available
Mighty,Module,MM1020,DC Input,Dual Limit Alarm,Two,SPDT,Relays,Fixed,Range Choice of Power Options
Mighty,Module,MM1020,DC Input,Dual Limit Alarm,Two,SPDT,Relays,Fixed,Range 10 + 5 Year Warranty

Typical Applications

DC motor/current limit, level/position control, HI/LO pressure alarm, power demand warning.

Mounting

The module is designed to plug into a standard 11-pin relay socket.  Part number MP011 is a molded plastic socket suitable for mounting on a flat surface on a 2 3/4 inch wide PVC snap track (TRK48). Use CLP-1 hold-down clip, if needed, with standard Module. A Killark HK Series explosion-proof housing with dome and 11-pin socket is available.  Order HKB-HK2D-11 (standard dome) for use with MM1020.  A DIN rail socket (part number DMP011) is available for 35mm symmetrical rail.

Specifications

INPUT RANGE
Voltage
  select any range between ±250 V max
    (min span 50 mV)

Current
  select any range between ±5 A max
    (min span 1 mA)

INPUT IMPEDANCE
Voltage
  200 kilohms

Current

Input
1 mA
10 mA
20 mA
4/20 mA
100 mA
1 A
5 A
Shunt Value
100 OHM
10 OHM
5 OHM
61.9 OHM
1 OHM
0.1 OHM
0.01 OHM

SETPOINT
Each alarm
 
0 to 100% of span

DEADBAND
Standard
 
Fixed 0.5% of span

(Option A)
  0.5% to 100% of span

RESPONSE TIME
20 ms typical
WR < = 200 ms
  (range dependent)

ACCURACY
±0.01% of span

COMMON MODE REJECTION
120 dB, DC to 60 Hz

RELAY CONTACTS
2 (spdt)
Resistive Load:
  5 A max, 150 W max
  220 VAC max, 30 VDC max

Inductive Load
  1/8 HP max at 120/240 VAC

TRANSISTOR OUTPUT (Option V)
Relay driver
  (12 V coil, > = 220 ohms)
or open-collector outputs
  sink 100 mA, 30 V supply max

LINEARITY (Option T)
±0.01% of span

OPERATING TEMPERATURE
 14°F to 140°F
-10°C to  60°C

TEMPERATURE STABILITY
±(0.02% of span + 30 µ V)/°C max

POWER
115 VAC 10%, 50/60 Hz
  (2.5 W max)
230 VAC 10%, 50/60 Hz
  (2.5 W max)

DC Power Option
  24 VDC (limits 21-32 VDC)
  Isolation, DC power supply to input common
    10 megohms

 

* Within specified range limits


CONNECTIONS
Power, AC L1 or DC +
Power, AC L2 or DC -
Input +
Input -
Relay 1 NO
Relay 1 C
Relay 1 NC
Relay 2 NO
Relay 2 C
Relay 2 NC
PINS
1
3
4
5
6
7
8
9
10
11