RTD,Input,Wireless,Transmitter,sensoRAD,DR9051R-03,Wilkerson Instrument

RTD Input Wireless Transmitter sensoRAD™ DR9051R-03


RTD Input Wireless Transmitter

DR9051R-03RTD,Input,Wireless,Transmitter,sensoRAD,DR9051R-03,Wilkerson Instrument

 

RTD,Input,Wireless,Transmitter,sensoRAD,DR9051R-03,Wilkerson Instrument

Features:

  • Direct 3 Wire RTD Input - Linearized Output
  • Four Discrete Inputs
  • 902 - 928 MHz ISM Unlicensed Band Standard
  • 2.4 GHz Unlicensed Band Available
  • Spread Spectrum, Frequency Hopping Technology
  • Repeater Capability
  • User Selectable HOP Sequence
  • Ranges to 20 Miles
  • Convenient DIN Rail Mount
  • 5 Year Warranty (1 Year on Radio Module)
  • UL/cUL Recognized

Description:

The DR9051R is an RF transmitter that will accept both analog and switch contact inputs. A 12 bit A/D converter is used to digitize the analog data. Analog data and switch status is then read when polled by the companion DR9050 Master Control Unit. The DR9050 MCU, under the control of a Modbus controller such as a PLC, polls the DR9051R and outputs the data in Modbus RTU format. A single DR9050 can poll up to 247 DR9051R’s utilizing a single Hop sequence.

The switch inputs require a standard contact closure or an open collector NPN transistor.

The DR9051R has a Repeater capability that allows it to pass data to and from an obstructed DR9051R.

Two different RF modules, which operate on different frequencies, are available for the 900 MHz band. Each has 7 hop sequences. With this choice, a total of 14 hop sequences are available.

The radio transmitter outputs 100mW (20 dBm) in the 902 to 928 MHz unlicensed ISM band. It uses frequency hopping, spread spectrum technology to allow multiple transmitters to work in the same locale without interference. A DIP Switch on the PC board is used to set the hopping sequence.

With proper antenna and cable selection, the DR9051R can transmit up to 20 miles line of sight.

The DR9051R provides isolation between analog inputs, output, and power source. The isolation makes the product useful for measuring input signals with high common mode voltages and for breaking ground connections to eliminate ground loops.

Switch inputs pull a DC current through the LED of optoisolators. The excitation current is taken from the DC power source. The power source is isolated from the overall circuit by a transformer coupled power supply.

Screw terminal blocks that plug into the case allow easy wiring and removal of products.

All of the DR Series of products provide transient protection to help eliminate damage from lightning and from other transients created on the power and signal leads.

Specifications

INPUT
100 Ohm Platinum RTD, 3 wire

  • .00385 or .00392 alpha

Range

  • -200 to +850°C Maximum
  • 15°C Span Minimum

Accuracy

  • ±0.1% of span

Linearity

  • ±0.05% of span

COMMON MODE REJECTION

  • 80 dB, DC to 60 Hz

Switch Input

Open Circuit Voltage

10 to 30 VDC

Closed Circuit Current

3 to 9 mA

OPRATING TEMPERATURE

  • -13°F to 167°F/-25°C to 75°C

TEMPERATURE STABILITY

  • ±(0.01% of span)/°C max

POWER

  • 10 to 30 VDC, 12VDC, or 24VDC 1.5 Watts Max

RADIO
Frequency

  • 910 - 917 MHz (Standard)
  • 920 - 927 MHz (Optional)
  • 2.4000 - 2.4835 GHz

Spread Spectrum Type

  • Frequency Hopping, Direct FM
  • 7 Hop Sequences

I/O Data Rate Tx to Rx:

  • Update Rate - 5/S

Range (Line of Sight)

  • 900 MHz -- Up to 20 mi. with high gain antennas
  • 2.4 GHz - Up to 10 mi. with high gain antennas

Receiver Sensitivity

  • -110 dBm (900 MHz)
  • -105 dBM (2.4 GHz)

Transmitter Power:

  • 100 mW (20 dBm)

Connector:

  • Reverse Polarity SMA Female

Certification:

  • RF Module -- FCC Part 15.247
  • DR9051R UL/cUL Recognized

* NOTE: This unit must be used with a DR9050 Master Control Unit.