AC,True,RMS,Input,Isolated,Field,Rangeable,Transmitter,Model DM6010,Wilkerson Instrument

AC True RMS Input Isolated Field Rangeable Transmitter Model DM6010


TERMINAL CONNECTIONS
Power AC L1 or DC +
Power AC L2 or DC -
Input
Input
Input Common
Shield
Output +
Output -
(Terminal Labeled)
L1
L2
1
2
3
4
Output +
Output -
AC,True,RMS,Input,Isolated,Field,Rangeable,Transmitter,Model DM6010,Wilkerson Instrument

AC,True,RMS,Input,Isolated,Field,Rangeable,Transmitter,Model DM6010,Wilkerson Instrument

Features

AC,True,RMS,Input,Isolated,Field,Rangeable,Transmitter,Model DM6010,Wilkerson Instrument Spans from 0.016 V rms to 256 V rms
AC,True,RMS,Input,Isolated,Field,Rangeable,Transmitter,Model DM6010,Wilkerson Instrument Provides a Fully Isolated DC Output Proportional to the True rms of the AC Input
AC,True,RMS,Input,Isolated,Field,Rangeable,Transmitter,Model DM6010,Wilkerson Instrument Plug-in Terminal Blocks
AC,True,RMS,Input,Isolated,Field,Rangeable,Transmitter,Model DM6010,Wilkerson Instrument Standard DIN rail Mount With Easy Snap-on Snap-off
AC,True,RMS,Input,Isolated,Field,Rangeable,Transmitter,Model DM6010,Wilkerson Instrument Connections and Ranging Readily Accessible From The Front
AC,True,RMS,Input,Isolated,Field,Rangeable,Transmitter,Model DM6010,Wilkerson Instrument User-Settable Input and Output Ranges
AC,True,RMS,Input,Isolated,Field,Rangeable,Transmitter,Model DM6010,Wilkerson Instrument User Write-on Label
AC,True,RMS,Input,Isolated,Field,Rangeable,Transmitter,Model DM6010,Wilkerson Instrument Fully Labeled Jumper Positions for Easy Range Settings
AC,True,RMS,Input,Isolated,Field,Rangeable,Transmitter,Model DM6010,Wilkerson Instrument Choice of Power Options
AC,True,RMS,Input,Isolated,Field,Rangeable,Transmitter,Model DM6010,Wilkerson Instrument Permanent Warranty
AC,True,RMS,Input,Isolated,Field,Rangeable,Transmitter,Model DM6010,Wilkerson Instrument UL, cUL Recognized

Description

The DM6010 provides an isolated voltage or current output proportional to the RMS value of an AC voltage or current input.  The true RMS measurement capability allows accurate measurements of distorted sine wave sources as well as complex wave shapes such as a phase angle modulated SCR drive output.

The DM6010 includes filtering and conditioning to reduce susceptibility to transients and noisy operations. It utilizes a feedback VCO to develop a pulse train with a duty cycle proportional to the input signal amplitude. This pulse train is coupled through a pulse transformer to the output circuitry, where the duty cycle data is converted to a proportional DC output level.

Connections are made via two 4-pin plug-in terminal blocks. These terminal blocks allow the product to be removed without unwiring the connections.

Typical Applications

Useful for motor control, accurate AC measurements, and data acquisition.

Mounting

The module mounts on a standard H-35 DIN rail. A spring latch holds it in place. The module is demounted by using a screw driver to release the latch. The latch release is accessible at the bottom of the module.

Specifications

INPUT
Span
  Voltage
    0.016V to 256V
  Current
    0.8 mA to 100 mA

Frequency
  47 Hz To 1000 Hz

Span Adjustment
  +5% to -55% of selected range

Zero Adjustment
  50% elevated

Impedance
  Voltage
    1 megohm
  Current
    20 ohms

Crest Factor
  PEAK/RMS = 6.3 max
  (±1% accuracy)

POWER 
 Wattage 2.5 W maximum

AC (Standard)
  115 VAC ±10%, 50/60 Hz
  230 VAC ±10%, 50/60 Hz
   24 VAC ±10%, 50/60 Hz

DC (Optional)
  24 VDC  (21-32 VDC)

APPROVALS
UL, cUL Certified

OUTPUT
Voltage
0/.25
0/1
1/5
0/5
0/10
-5/5
-10/10
Current (mA)
0/1
0/4
4/20
0/20

OUTPUT LOGIC
Normal or Reverse Acting

DRIVE CAPABILITY
Voltage
  5 mA
Current
  >24 compliance

ACCURACY
±0.3% of span

OUTPUT RIPPLE
<0.1% of full scale
  (peak to peak)

OPERATING TEMPERATURE
 14°F to 140°F
-10°C to  60°C

TEMPERATURE STABILITY
±(0.01% of span)/°C

ISOLATION
Resistance
  >500 megohms

Voltage Rating
  >1000 VAC sine wave