DC Input,Field Rangeable,Isolated,Transmitter,Model DM4380A

DC Input Field Rangeable Isolated Transmitter Model DM4380A


TERMINAL CONNECTIONS
Power AC L1 or DC +
Power AC L2 or DC -
Input +
Input -
Shield
Output +
Output -
(Terminal Labeled)
L1
L2
Input +
Input -
SHLD
Output +
Output -
DC Input,Field Rangeable,Isolated,Transmitter,Model DM4380A

DC Input,Field Rangeable,Isolated,Transmitter,Model DM4380A

Features

DC Input,Field Rangeable,Isolated,Transmitter,Model DM4380A Allows Inputs to +\-256 V or +\-100 mA
DC Input,Field Rangeable,Isolated,Transmitter,Model DM4380A 15 mV or 0.8 mA Minimum Full Scale Input
DC Input,Field Rangeable,Isolated,Transmitter,Model DM4380A Provides a Fully Isolated DC Output Proportional to DC Input
DC Input,Field Rangeable,Isolated,Transmitter,Model DM4380A Plug-in Terminal Blocks
DC Input,Field Rangeable,Isolated,Transmitter,Model DM4380A Standard DIN rail Mount With Easy Snap-on Snap-off
DC Input,Field Rangeable,Isolated,Transmitter,Model DM4380A User-Settable Input and Output Ranges
DC Input,Field Rangeable,Isolated,Transmitter,Model DM4380A Fully Labeled Jumper Positions for Easy Range Settings
DC Input,Field Rangeable,Isolated,Transmitter,Model DM4380A Connections and Ranging Readily Accessible From The Front
DC Input,Field Rangeable,Isolated,Transmitter,Model DM4380A Choice of Power Options
DC Input,Field Rangeable,Isolated,Transmitter,Model DM4380A User Write-on Label
DC Input,Field Rangeable,Isolated,Transmitter,Model DM4380A Permanent Warranty
DC Input,Field Rangeable,Isolated,Transmitter,Model DM4380A UL, cUL Recognized

Description

The DM4380A provides a DC output proportional to a DC input. The output is fully isolated from input, line power, and ground. The unit is useful in eliminating ground loops and common mode signals.

Input and output ranges are user-settable. Each may be voltage or current, with or without offset. The output response may be normal or reverse-acting. A fully-labeled set of jumpers selects the input and output ranges.

The DM4380A includes filtering and conditioning to reduce susceptibility to transients and noisy operations. It utilizes a feedback VCO to develop a pulse train with a duty cycle proportional to the input signal amplitude. This pulse train is coupled through a pulse transformer to the output circuitry, where the duty cycle data is converted to a proportional DC output level.

Connections are made via two 4-pin plug-in terminal blocks. These terminal blocks allow the product to be removed without unwiring
the connections.

Typical Applications

Eliminates ground loops and common mode signals for voltage/current scaling or conversion, isolation, buffering, noise reduction. Single-unit replacement module provides all normal input and output ranges.

Mounting

The module mounts on a standard H-35 DIN rail. A spring latch holds it in place. The module is demounted by using a screw driver to release the latch at the bottom of the module.

Specifications

INPUT RANGE
Limits
  (User Settable)
  any voltage between -256 and +256 VDC
  any current between -100 and +100 mADC

Span
  Voltage
    Any voltage span from 15 mV to 256V
  Current
    any current span from 0.8 mA to 100 mA

LINE OFFSET
±0, 25, 75,  100% of F.S.

INPUT IMPEDANCE
Voltage
  1 megohm
Current
  20 ohms

POWER 
 Wattage 2.5 W maximum

AC (Standard)
  115 VAC ±10%, 50/60 Hz
  230 VAC ±10%, 50/60 Hz
   24 VAC ±10%, 50/60 Hz

DC (Optional)
  24 VDC  (21-32 VDC)

ISOLATION
Isolation, Output / Input
  >500 megohms

Breakdown, Output / Input
  >1000 VAC RMS sine wave

Breakdown, Power / Circuitry
  >1500 VAC RMS Sinewave

COMMON MODE REJECTION
>120 dB, DC to 60 Hz

APPROVALS
UL, cUL Certified

OUTPUT
Voltage
0/.25
0/1
1/5
0/5
0/10
-5/5
-10/10
Current (mA)
0/1
0/4
4/20
0/20

OUTPUT LOAD
Voltage
  10 mA max (1 kilohm at 10 V)
Current
  24 V compliance (1200 ohms max at 20 mA)

ACCURACY
±0.1% of span
  (exclusive of user-supplied 
  calibration instruments)

LINEARITY
±0.05% of span

OUTPUT RIPPLE
<0.1% of span
  (peak to peak)

OUTPUT RESPONSE
normal or reverse-acting
  (User settable)
  (example 10 to 0 VDC)

RESPONSE TIME
<100 ms

OPERATING TEMPERATURE
 14°F to 140°F
-10°C to  60°C

TEMPERATURE STABILITY
±(0.02% of span + 2 µV)/°C